Ultrasonic Flowmeter
Ultrasonic Flowmeter (FUM-1000Series)
FUM-1000 Series measures the velocity of the fluid by time difference. By adding temperature sensor, it also measure calories. It can inserts or attaches sensor by socket weld or band.
It has algorithm to measure the sensor signal strength and align the the distance between sensor precisely. So we can attach the sensor easily.
- FUM-1000C (Clamp on Type)
- FUM-1000I (Insert Type)
- CATALOG
- FUM-1000C
- FUM-1000I
- MANUAL
- TEST REPORT
Specifications
Type | Clamp-on Type, Insertion Type |
---|---|
Theory of Measurement | Transit Time Difference |
Flow Range | 'S' Sensor : 15 ~ 100mm(1/2 ~ 4") |
'M' Sensor : 50 ~ 700mm(2 ~ 28") | |
'L' Sensor : 300 ~ 6,000mm(12 ~ 240") | |
Sensor Installation | 'V' Method(50 ~ 350mm) |
'Z' Method (*'W', 'I' Method는 소형 배관 적용) | |
Pipe Material | Steel, Stainless Steel, Cast Iron, Plastic, etc.(20 ~ 6,000mm) |
Lining Material | Tar Epoxy, Rubber, Mortar, Polyprolylene, Polystryal, Polystyene, Polyester, Ebonite, Polyethylene, Teflon, etc. |
Transmitter Mounting | Wall Mounting |
Display |
|
Accuracy | ±1% ~ ±2% of reading(0.5 ~ 30m/s) ±0.5% of reading(Online Calibration) |
Repeatability | ±0.2% ~ ±0.5% 0 ~ 16m/s(R.D.) |
Keypad | 16 Key with tactile action |
Response Time | Less than 1 second |
Flow Velocity | 0.01 ~ ±32m/s(Forward & Reverse) |
Resolution | 0.0001m/s |
Ambient Temperature | -20 ~ +50(Option : ~ +120℃) |
Max. Cable Length | 150m |
Power Consumption | Less than 2w |
Power Supply | AC 90 ~ 260V 50/60Hz |
Data Storage | Operation parameters and totalization date are stored by EEPROM for more than 10years |
Output | 4 ~ 20mA or 0 ~ 20mA |
Pulse Output | 1 ~ 9,999Hz |
Date Logger (Option) | 64 data include flowrate, totalizer, time, date |
Alarm | High/Low with Buzzer |
Communication | RS-485 |
Transmitter Dimension | 213(W)×184(H)×105(D)mm |
Transmitter Weight | 1.5Kg |
Enclosure | Transmitter : IP65 |
Sensor : IP67(Submersible) |